Low subcool low superheat - Superheat and subcooling are two important concepts in HVAC. Superheat is the number of degrees a vapor is above its boiling point at a specific pressure. Subcooling, on the other hand, is the number of degrees a liquid is below its freezing point at a specific pressure. ... Conversely, if the superheat is too low, it could mean that the ...

 
High pressures can cause refrigerant leaks at the condenser, leading to high superheat and low subcooling. To avoid these issues, ensure sufficient airflow by keeping condenser coils and fins clean. 2. Malfunctioned Metering Devices. The metering tool controls the refrigerant flow. A malfunctioning tool can result in refrigerant flow .... Zac love island australia birthday

a txv is what maintains superheat for the evap coil. We have taken our superheat measurement. And should know if the superheat is very high no refrigerant is passing the txv. And if it's very low too much is passing. We can then test the txv bulb. Remove it from the system and hold it in your hand to warm it up watch the superheat go down.A) drain the oil from both compressors B) drain the oil from the compressor being evacuated C) close the oil equalization connection D) flush the oil equalization line with nitrogen, _____ indicates low charge in a high-pressure system with a capillary tub A) Low superheat B) Low subcooling C) excessive superheat D) excessive vibration, After ...In this HVAC Video, I Explain Superheat and Subcooling in the Refrigeration Cycle to Understand the Operation Easier! I go over how to understand the importa...On traditional HVAC/R systems, which utilize mechanical metering devices such as a TXV or cap tube, the superheat heating will vary between 8 °F to 20 °F. On newer systems, which use electronic expansion valves and solid state controllers, it is possible to see the superheat setting as low as 5 °F to 10 °F.May 25, 2013 ... Comments265 ; Why and How to Adjust a TXV / TEV. HVAC School · 413K views ; Superheat and Subcooling Explained! How to Easily Understand! AC ...Lowes.com is the official website of Lowe’s Companies, Inc., one of the largest home improvement retailers in the world. The website was launched in 1996 as a way for customers to ...CAUSE #2: Defective, plugged, or undersized metering device. Let's say a system has 45 psi suction pressure (converts to 22 ° F) and 68 ° F suction line temperature, the superheat is 46 ° F (68 minus 22). This indicates low refrigerant in the evaporator. However, before adding refrigerant, check the subcooling to be sure the problem isn't ...The best answer is—as usual—whatever the manufacturer says it should be. If you really NEED a general answer, you can generally expect: High Temp or A/C systems to run 6-14°F of superheat. Medium Temp - 5-10°F. Low Temp - 4-10°F. Some ice machines and other specialty refrigeration may be as low as 3°F of superheat.Low Subcool. High Superheat (potentially) Low Evaporator Delta T. Poor Dehumidification due to high coil temperature. Low compressor amps. Low Compression Ratio. Low Discharge Temperature. Low Approach (liquid line temperature above outdoor temperature) High Efficiency (EER/SEER) High Stage (5-ton)It's simply shedding heat energy, moving left all the way through the saturation dome, and even subcooling the refrigerant slightly at the end. Point 3: The "throttle" is the metering device that separates the high-pressure condenser from the low-pressure evaporator -- usually a thin capillary tube in household refrigerators. As the refrigerant ...The system below is a walking freezer with a TEV. Refrigerant is R404a. Standard conditions are -10 °F box temperature for freezing (low temperature); 10 °F evaporator TD; 25 °F condenser split; 10 °F superheat; and 10 °F subcooling. From the information given on the diagram, answer the question below.Subcooling is beneficial because it prevents the liquid refrigerant from changing to a gas before it gets to the evaporator. Pressure drops in the liquid piping and vertical risers can reduce the refrigerant pressure to the point where it will boil or "flash" in the liquid line. This change of phase causes the refrigerant to absorb heat before ...In this HVAC Video, I Show SEVERELY UNDERCHARGED, UNDERCHARGED, CORRECTLY CHARGED, and OVERCHARGED Scenarios on a Running R-410A Refrigerant Air Conditioner ...Too little charge will lead to low suction pressure and evaporator freezing. As a general rule, lower ambient temperature = increased sub-cooling. There is a stronger relationship between superheat and evaporator load then there is between superheat and ambient temperature - although obviously evaporator load is a function of ambient.Low Subcooling • Low on charge • Metering device allowing too much refrigerant flow; piston too large, TXV failing open, piston seating improperly ... Low temperature difference between the boiling point and superheat = low superheat (Below the normal 8-12 deg you should be seeing.. like a 3-7 degree temperature difference.) 1 …First, measure the superheat right at the evaporator outlet in the same general location as the TXV bulb and equalizer. In most cases, the superheat at that point should be 5-10 degrees, but refer to the manufacturer's specs when in doubt. In some cases, you will not have a pressure port at the evaporator, so you must rely on a pressure reading ... To check subcooling, attach a thermometer to the liquid line near the condenser. Take the head pressure and convert it to temperature on a temperature/pressure chart. Subtract the two numbers to get the subcooling. For example, 275 psi head pressure on an R-22 system converts to 124°F. The liquid line temperature is 88°F. One of the most common reasons for low superheat is due to reduced airflow. With reduced airflow, there isn't enough warm air to vaporize the refrigerant. What does low Subcool mean? Low Subcooling is an indication that not enough refrigerant is contained or "packed" in the condenser. This can be due to undercharge, poor compression, or a ...SUPERHEAT/SUBCOOL CALCULATOR with Thermometer and P/T Chart (69196) OPERATING STEPS. 1. Press the power button. For SuperHeat or Low Side PT Data. Suction Line "Super Heat" Match low side manifold gauge reading (suction pressure) 2. Use the and to display the desired refrigerant. 3. Press ENTER. For SubCool or High Side PT Data. Liquid Line 4.The Evaporator Superheat Method should be the first effective method of properly charging a capillary tube or a fixed orifice/actuator piston as refrigerant metering device. Install your pressure gauges to the outdoor condensing unit. In the air conditioning mode this would be the compound, low-pressure gauge to the suction (vapor) refrigerant line at its service valve.High Superheat Can Be Caused By Undercharge Of refrigerant, Excessive Load (Just starting Up The system), Liquid Line Restriction (Like Filter Drier Clogged), Underfeeding Metering Device Low Subcooling Can Be Caused BySubcooling is a measurement of how much the liquid in the condenser cools down before exiting. When the hot gas in the condenser first turns to liquid, its temperature is at the saturation point. This means that the temperature of the liquid as it first forms is at the same temperature at which the refrigerant is condensing — the saturation ...The best answer is—as usual—whatever the manufacturer says it should be. If you really NEED a general answer, you can generally expect: High Temp or A/C systems to run 6-14°F of superheat. Medium Temp – 5-10°F. Low Temp – 4-10°F. Some ice machines and other specialty refrigeration may be as low as 3°F of superheat.What is the primary reason for running the suction and liquid lines in physical contact with one another? (A) Separate oil from the refrigerant in the suction line. (B) Reduce installation cost. (C) Superheat liquid refrigerant before the expansion valve. (D) Sub-cool the refrigerant in the liquid line.Over Charge- If refrigerant charge is high, the superheat will be low. The low side pressure will be higher than normal. This indicates the refrigerant did not absorb enough heat to properly change to a vapor. Liquid refrigerant may enter the compressor if superheat is too low. Dirty Evaporator Coil- A dirty air filter, evaporator coil or lack ...At a high level, superheat occurs when you heat vapor above its boiling point. Subcooling occurs when you cool a vapor below the temperature at which it turns into a liquid. But let's dive in deeper, starting with superheat. Boiling is when a liquid gains heat and transforms into a vapor. Remember, superheat occurs when you heat vapor above ...If it does it in decent weather: It's airflow. Or, more accurately a lack of heat load on the evap. Your txv has bogged all the way down, creating a high subcool. It's bogged so far down, and still can't maintain a decent superheat. This is from your low evap temp, low sh and high subcool.Both are out of cooling. and both have high superheat. like suction 20psi -7F, suction line temp 78F, head pressure 190psi, 97F, liquid line temp 72F, out door dry bulb temp 73F, Wet bulb at register indoor 19F, indoor dry bulb temp at register 78F. At the start of the suction.Maryland. Posts. 9. Post Likes. Low Subcooling Low Superheat? I am working on a two stage heat pump with a varable speed air handler. The system runs about 1.5 deg S/C and about 2 deg S/H The delta T is 22 deg. A capacity check shows systems is operation at 122% of publish Capacity. Adding refregerant does not change the S/C much at all.Many reasons can cause subcooling to occur, including underfeeding, overcharging, restricted meter device, or faulty head pressure control. The effect of subcooling is …Take the condensing temperature and the condenser outlet temperature, and the difference between the two is the amount of subcooling. “Let’s say the condensing temperature is 100°F. Put a thermistor on the condenser outlet, and let’s say that’s 90°,” continued Tomczyk. “So, you have 10° of subcooling. Technicians get confused ...From the Goodman manual for that model. Outside drybulb 95F inside drybulb 80F. Hi pressure = 335 Psig, Lo pressure 130 Psig. Which is 20-30 psi off on both. But I was under the assumption if it where low on 410a there would be high superheat and high subcooling. Like I said I'm new. With the excessive subcooling and no superheat, I am confused.Jul 3, 2013 · High Subcool Low Superheat. Hi I own two wonderful Trane wethertron heat pumps"8 seer". 85 degree day 115 condensing temp. Low side was 65 psig High side 240 psig. 6.5 superheat and 25 degree subcooling. My first assumption was overcharge due to poor winter performance energizing aux heat strips a lot. Right now in cooling I have a 17 degree ... Actual Box Temp. Cond Temp should be ±10∘F Actual Cond Temp = Cond Subcooling = (2) Actual Evap Temp = (1) Evap Temp should be TEV 80∘. Question: (7) Symptoms Service Problem 7-4 Cond. Temp: High Low Normal - Walk-in FREEZER Subcooling : High Low Normal - R404A Evap. Temp : High Low Normal - TEV Superheat : High Low Normal (9) Repair ...The increase in temperature above saturation is described as the refrigerant’s superheat value. For example, at 18.42 psig, R-134a has a saturation temperature of 20°F. If its measured temperature is 30°F, the refrigerant is said to be superheated by 10°F. One useful area to measure the refrigerant’s superheated value is at the exit of ...If the head pressure drops too low due to low ambient conditions, this can come into play and impact the ability of the valve to do its job. Once this is all confirmed, then it is simply a matter of checking the superheat at the end of the evaporator. Most A/C systems will maintain 6-14° of superheat at the evaporator outlet.Subcooling is when the liquid refrigerant in your is colder than the minimum temperature required to keep it from boiling. This can happen when the system is first turned on, or if there's a problem with the system. When this happens, the liquid refrigerant can change from a liquid to a gas phase, which can cause problems with the HVAC system.Over Charge- If refrigerant charge is high, the superheat will be low. The low side pressure will be higher than normal. This indicates the refrigerant did not absorb enough heat to properly change to a vapor. Liquid refrigerant may enter the compressor if superheat is too low. Dirty Evaporator Coil- A dirty air filter, evaporator coil or lack ...low superheat negitive subcooling I went on a service call on a whirlpool split system (straight A/c) the other day and found the compressor pulling locked rotor, installed hard start kit and the compressor started for a few seconds and went back to pulling LRA. ... I think thast if your subcool was realy negative then all the refrigerant ...In this HVAC Video, I Explain Superheat and Subcooling in the Refrigeration Cycle to Understand the Operation Easier! I go over how to understand the importa...a txv is what maintains superheat for the evap coil. We have taken our superheat measurement. And should know if the superheat is very high no refrigerant is passing the txv. And if it's very low too much is passing. We can then test the txv bulb. Remove it from the system and hold it in your hand to warm it up watch the superheat go down.To check subcooling, attach a thermometer to the liquid line near the condenser. Take the head pressure and convert it to temperature on a temperature/pressure chart. Subtract the two numbers to get the subcooling. For example, 275 psi head pressure on an R-22 system converts to 124°F. The liquid line temperature is 88°F.System Information R22 2.5 ton: Low Side: 115. High Side: 240. Return Air: 83. Suction Line Temp: 75. Measured Super heat: 5. Super heat should be around 15. Low superheat is an indication that liquid refrigerant not changing state in the evaporator and is possibly flooding back to the compressor.Originally Posted by Brad gall. .12 degree subcooling and 0 on the superheat both measured at the condenser.. This just don't make sense to me, you would think with only a 12° SC if you were able to get that with a wide open valve, that there would be some flashing, and not have a 0 SH, heck you got me.Superheat is measured as the difference between the actual temperature of refrigerant vapor at a certain point and the saturation temperature of the refrigerant. It’s not complicated, but for a beginning tech, it might be.”. Superheat may be so complicated just because of the term “heat,” Tomczyk said. “Because something can be minus ...1. a) Most walk-in coolers and freezers use a TX valve to regulate the flow of refrigerant into the evaporator. If the superheat is low the TX valve will allow refrigerant to flow into the evaporator at a rate that exceeds the capacity of the evaporator and as a result liquid will enter the suction line. One sign of low subcooling is high suction pressure in your HVAC system. When there’s not enough subcooling, the refrigerant pressure in the system can become elevated, which can lead to poor cooling performance and potential damage to your system. Low discharge pressure. Low discharge pressure is another sign of low subcooling. Note: The unit will not display a negative superheat or subcool temperature. "--" will display instead. Make sure you have the proper temperature clamp location (Step 4) and the proper pressure value (Step 5). Suction Line Liquid Line Match low side manifold gauge reading (suction pressure) "Super Heat" "Sub Cool"Liquid line temp 101 degrees and the suction was 49 degrees. The low subcooling and low suction pressure indicate low airflow. The somewhat low deltaT seems to contradict that. Could be a significant amount of air bypassing the coil based on your report, which would account for all of the numbers that you posted.The condenser subcooling will be normal to a bit high because of this. The refrigerant flow rate will be low through the system from the restriction. This will cause what refrigerant there is in the condenser to remain there longer and subcool more. Note that an undercharge of refrigerant will cause low subcooling. Low Evaporator PressuresThe most important values for checking to superheat and subcool are the endpoints of the glide or the pressure-temperature relationship for saturated liquid and saturated vapor. ... Some of the zeotropic blends have very low glide (from I° F to 2.5° F). For these blends, the vapor and liquid pressures are only separated by 1 or 2 psi. ...A low suction superheat does not 'indicate' an overcharge. Low suction superheat is the result of too much refrigerant in the evaporator for the heating loading of the evaporator at that moment in time. Post the startup report data: Outdoor Ambient temperature. Condenser air temp in. Condenser air temp out.Low superheat in HVAC can be caused by factors such as low refrigerant charge, a faulty expansion valve, or insufficient heat load on the evaporator. What is normal superheat for 410a? Normal superheat for R-410A systems can range from 5-25°F (2-14°C) depending on the specific system and operating conditions.Low superheat and high subcooling. What does an undercharge cause? High superheat and low subcooling. What method is used to correctly charge a TXV system? Subcooling method. Which is a fixed orifice metering device? AXV, Piston, TXV, and EEV. Piston. Does an overcharged unit have low or high amp draw?Robo stated it clear, the normal superheat for a residential system can and will vary and some charts go even further than he stated 2-45 degrees. That answer above drives the point, if you do not know the evaporator load, you can not predict the superheat. Reply. 06-02-2011, 06:58 PM #14. hvacvegas.October 10, 2000. Different types of metering devices have different ways of charging. An air conditioning unit with a thermostatic expansion valve (TXV) is charged to the subcooling of the liquid line leaving the condenser because the superheat is fixed. The superheat is fixed at 8°F to 12°F in most residential air conditioning systems.A low subcooling and a high superheat. An air conditioner with a fixed restriction metering device is operating with an evaporator saturation temperature of 40 degrees Fahrenheit and a suction line temperature of 42 degrees Fahrenheit. The factory specified superheat for the current operating condition is 12 degrees Fahrenheit.Sep 4, 2021 ... Superheat = Difference between Evap Temperature and Suction Pipe Temperature. To measure the superheat of the Air Conditioning system, ...Even if a system charge is available, you want to check superheat. And you want to check subcooling, more so as a reality check. 30ºF subcooling suggests to me that your orifice is too small. If we have data, let's look at data. If all we have are opinions, let's go with mine. - Jim Barksdale, former Netscape CEO.To measure liquid subcooling: 1. Attach your gauge manifold to the liquid line service port. If you use a quick-connect fitting on the end of your hose, make sure it’s a low-loss fitting. I’ve seen some quick-connect fittings that allow pressure loss, which can cause inaccuracies in the charging procedure.The low Pressure gauge (blue) is used to calculate superheat. A superheat reading of 10F measured at the evaporator outlet, would indicate that the refrigerant at that location is in what condition.. The refrigerant is a vapor (gas).Opening a small business isn't easy. Getting a small business off the ground with little to no budget is an even more challenging feat. Opening a small business isn’t easy, even wh...Part 1 of this article covered how to calculate total temperature glide, effective temperature glide, fractionation, average evaporator and condenser temperature, evaporator superheat, and condenser subcooling for refrigerant blends that have a temperature glide. This article will offer a quick review of evaporator superheat and condenser subcooling calculations, then create a scenario where a ...Yes, high superheat and low subcooling can harm your HVAC system. High superheat levels can cause the air conditioning system to deliver less cooling. It can also cause the compressor to overheat ...Low subcooling means that a condenser is almost empty. High subcooling means that a condenser is over field of liquid. 1) The amount of refrigerant entering the metering orifice is the Outdoor Dry bulb. 2) The total heat of the air entering the evaporator coil is the Indoor Wet bulb. With 95 degrees outside air.Calculate. This free online tool allows HVAC professionals to quickly calculate Superheat and Subcooling measurements for both R22 & R410A refrigerants.Lowes is a well-known home improvement retailer that offers a wide range of products, including appliances. Whether you’re renovating your kitchen or looking to upgrade your curren...Low subcooling means that a condenser is almost empty. High subcooling means that a condenser is over field of liquid. 1) The amount of refrigerant entering the metering orifice is the Outdoor Dry bulb. 2) The total heat of the air entering the evaporator coil is the Indoor Wet bulb. With 95 degrees outside air.Superheat and subcooling data can help you pinpoint these issues quickly. Common Causes of Superheat and Subcooling Imbalance. Common reasons for superheating and subcooling include issues such as liquid line restriction, malfunctioning metering systems, and limited airflow, all of which can lead to high superheating and low subcooling levels. 1.Bryan with HVAC School goes over AC pressures, subcooling, and superheat in his troubleshooting mindset presentation from the BTrained HVAC training event in Birmingham, AL. Bryan also talks a bit about his educational photo-sharing app, MechPic. The suction pressure and suction saturation give us an idea of the refrigerant’s …For subcooling a ballpark range may be somewhere inbetween 10-15 degrees F. For superheat it could be 12-20 degrees F. Check with the manufacturer though. Many units have a charging chart, behind the name plate on the condensing unit, use this first. Charge by superheat for fixed metering devices, and use subcooling for TXV's, if your not ...Replace air filters and the blower wheel. Overfeeding of the metering device. Ensure sensing valve of the TXV is properly insulated. Insufficient heat load to the coil. Clean the filters and the coil. Oversized AC system. Consider going for a well Sized AC unit. Read also: How to Fix High Superheat Low Subcooling.The main reasons your compressor will have simultaneously low head pressure and high suction pressure is due to: Bad or leaky compressor valves. Worn compressor piston rings. Leaky oil separator return line. Your compressor valves may become inefficient due to poor sealing from dirt and debris deposits.High compressor superheat; Low condenser subcooling; Low compressor amps; Low evaporator temperatures and pressures; and; Low condensing temperatures and pressures. Again, the symptoms of a liquid line restriction are very similar to a system with a refrigerant undercharge; however, the undercharged system will have low condenser subcooling levels.On a txv system for comfort cooling superheat is commonly in the 10-15 deg. F range. anything outside of that range would be considered low or high. It of course is dependent on the valve superheat setting. This is all assuming that the system is running properly, there is not too much load on the evap, not too much load on the condenser and ...Dec 1, 2023 · Superheat, a critical aspect of an HVAC system, involves heat absorption and the use of refrigerants like freon. This process impacts the temperature regulation and the suction capabilities of your system, with a key role played by the liquid line. Let’s delve deeper into what superheat is, how it works, its relationship with refrigerants ... Low superheat, normal subcool, not cooling . Sorry for the long post, but I’m stumped. Got a call on a 3 ton carrier today(3yrs old, warranty, not our install). Another company diagnosed a bad TXV but wanted $1200 to replace the part, so the homeowner shopped around and hired us. ... 11.8 superheat, but only 13deg TD at the indoor unit. Run ...Low super heat, low subcool. Recovered some refrigerant out to reach target subcool but head pressure/superheat didn’t get anywhere I wanted to. A/c was installed a month ago and charge was dialed in before leaving. Any ideas before I …

Which would suggest 26 is high for the superheat and 61 is way high for the subcooling. The suction pressure and SST is normal, but 350 could be high for the head depending on the unit SEER. Residential 13 SEER equipment would be closer to 300 for an 80 degree ambient. It's about right for 10 SEER.. How to bail someone out of jail in maricopa county

low subcool low superheat

Bryan with HVAC School goes over AC pressures, subcooling, and superheat in his troubleshooting mindset presentation from the BTrained HVAC training event in Birmingham, AL. Bryan also talks a bit about his educational photo-sharing app, MechPic. The suction pressure and suction saturation give us an idea of the refrigerant’s …High superheat in a refrigeration system occurs when there is a limited amount of refrigerant in the evaporator for the heat load that is present. High superheat indicates that. 1. Low levels of refrigerant. 2. restriction in the liquid line. 3.Calculating superheat can tell us how far liquid Freon is traveling through an evaporator coil. If superheat is too high, there’s less liquid and more gas in the coil. This can cause overheating. If superheat is too low, more liquid and less gas are in the coil. This can cause flooding and damage in the compressor.Low airflow can be caused by a dirty or clogged air filter or a malfunctioning fan or blower motor, so be sure to investigate those components as the source of insufficient airflow. Low refrigerant charge. As seen in the table in Figure 2, a low refrigerant charge will result in a higher superheat and a lower subcooling and lower evaporator ...Low superheat and high subcooling. What does an undercharge cause? High superheat and low subcooling. What method is used to correctly charge a TXV system? Subcooling method. Which is a fixed orifice metering device? AXV, Piston, TXV, and EEV. Piston. Does an overcharged unit have low or high amp draw?May 25, 2013 ... Comments265 ; Why and How to Adjust a TXV / TEV. HVAC School · 413K views ; Superheat and Subcooling Explained! How to Easily Understand! AC ...An HVAC system is said to be running with high superheat or low subcool when there is a limited amount of refrigerant in both the evaporator coils and in the compressor. The possible reason for the high superheat and low subcool could be due. 1. Restriction in the liquid line. 2. Faulty metering system. 3. Excessive airflow through the ...a txv is what maintains superheat for the evap coil. We have taken our superheat measurement. And should know if the superheat is very high no refrigerant is passing the txv. And if it's very low too much is passing. We can then test the txv bulb. Remove it from the system and hold it in your hand to warm it up watch the superheat go down.If we measure the temperature on the liquid line exiting the condenser coil then we know the end temperature after the refrigerant has lowered in temperature. Subtract the lower temperature measured on …High superheat means there’s a lot of refrigerant vapor, while low superheat means there’s almost none. In a properly operating system, you should have cool vapor leaving the evaporator that moves through the suction line, service valve, and into the compressor. There are two kinds of superheat to consider in this flow.Superheat and Subcooling are technical readings in an HVAC that measure the Freon (refrigerant) reading. Superheat measures the Freon boiling point in gas form while subcooling measures the Freon in liquid form below the evaporation level. To calculate superheat and subcooling measurements, a specific Mathematical chart is used, and the process ...What would make superheat go down but subcooling stay around 2.5° when adding refrigerant? Classic call about home not cooling well during middle of the day. Delta T is around 11°. Superheat was around 38° subcooling was about 2°, low head and suction pressure. I'm thinking oh it's just low on charge.Common Causes of High or Low Superheat. Superheat is a crucial factor in refrigeration systems that controls the temperature and pressure of refrigerants. It measures the amount of heat added to vapor from its boiling point at a particular pressure, indicating how well the evaporator coil transfers heat between refrigerant and air.Low superheat and low subcooling is an indication of an overfeeding metering device NOTE: These are just guidelines and INDICATIONS OF A SYSTEM PROBLEM, since other system problems may result in the appearance of these symtoms. Hope this helps. 0. don_144 Member Posts: 27. June 2005.A suction pressure temperature reading of 45ºF and a suction line temperature of 56ºF tell you that there is 11ºF of superheat. This reading, in particular, can also demonstrate that …Hi, I just put a new compressor on a gas pack. I charged it to the correct amount of refrigerant o the name tag. My ambient temp. is 100 degrees and the unit running with a high high side pressure a high suction pressure and high superheat and sub cooling. The indoor temp is 87 degrees. i was told that the high indoor temp is why my pressures and temps. are high.proper low- and high-side pressures, set superheat and subcooling temperatures, and to set pressure controls. The tempera-ture glide of a blend will determine how the PT chart will look. Therefore, a quick review of tem-perature glide from last month's arti-cle is necessary: • As a portion of a refrigerant blend works its way down the length.